1. Overview Settings
In the SETTINGS, the parameters are specified which the elproMONITOR software uses for the current monitoring task. These parameters contain settings for
>> Device settings - Here all I/O modules for ECOLOG-PRO, ECOLOG-NET and the alarm interface as well as associated digital inputs, digital outputs, sensors and sensor groups are parameterized.
>> Profiles - All profiles for sensor limits (alarms, warnings), sensor faults, digital input profiles, receiver profiles, time control profiles, data destimation profiles and data export profiles are managed here.
>> Program - This is where scheduled exports, comment templates, e-mail recipient lists, SMS, system malfunctions and licenses are parameterized and managed.
>> User - Here you can make settings for your own user profile.
1.1. User Interface
The Settings overview is opened by clicking on the "Settings" menu item. The default view is the existing >> sensors of the >> device settings.
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Anchor | ||||
---|---|---|---|---|
|
The Sensors overview is opened by clicking on the "Sensors" menu item in the Settings menu.
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
General:
Sensor name
Name of the sensor for monitoring with elproMONITOR and for easy identification in the reports. The sensor must be provided with a unique name.Sensor status
This is an information field that reflects the current state (Enabled / Disabled) of the sensor. This field cannot be changed. The sensor is activated / deactivated in the monitor manually or automatically during a calibration.
Connection:
I/O module
Selection list with the available I/O modules. The sensor must be assigned to one of these I/O modules.I/O module channel
Selection list with all channels available at this I/O module. The sensor must be connected to one of these channels to receive its measured values. Only the channels that are still free are listed.Associated digital output
Selection list with the names of the available digital outputs. The sensor activates a digital output directly in the event of an error. (e.g. of an ECOLOG-PRO 4DO).
Info |
---|
The parameterized internal contacts of ECOLOG-NET loggers (Alarm 1 and Alarm 2) cannot be controlled by elproMONITOR. |
Recording:
Recording interval
At a restart, the 1st measured value is recorded when the first full interval is reached.
The recording of the data is synchronous. All measured values and statuses are recorded simultaneously. The interval can be specified individually for each sensor. The intervals 1, 2, 3, 4 , 5, 6, 10, 12, 15, 20, 30 and 60 minutes are possible.
To correct the interval of an existing sensor, it must be deleted or decommissioned and then added again.
Note |
---|
The recording interval cannot be changed subsequently. |
Note |
---|
The two channels of ECOLOG-PRO 1THR and 2TH are interleaved. Once one of them has been defined, no other recording interval can be selected for the other one. |
Time control profile
With a >> time control profile, the sensor can be controlled time-dependently for monitoring by elproMONITOR. An already defined profile can be selected from this selection list.
Description:
Sensor ID
In addition to the sensor name, serves as a further parameter for identifying the sensor.
Info |
---|
For digital sensors (e.g. ECOLOG-PRO 1THR) the sensor ID can also be read out from the sensor |
Sensor note
Text field for entering sensor-related information.
Profile Set A and Profile Set B:
The profile sets are used to assign the following >> profiles.
Profile for alarms due to limit violations.
Profile for receiver in case of alarms
Profile for warnings due to limit violations.
Profile for receiver in case of warnings
Profiles for sensor malfunctions
Profiles for receivers in the event of sensor malfunctions.
Info |
---|
With >> Time control profiles it is possible to switch between Set A (default) and Set B. This is used to switch between different alarm limits, warning limits, evaluated sensor faults and the corresponding receiver groups. |
List of existing sensor groups to which the sensor can be added or from which it can be removed.
Info |
---|
The sensor must be assigned to at least one sensor group by clicking the "Add" button. |
Info |
---|
Sensors can also be assigned to several sensor groups, which are displayed under "Sensor group name". |
Anchor | ||||
---|---|---|---|---|
|
The digital inputs overview is opened by clicking on the "Digital inputs" menu item in the Settings menu.
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
General:
Digital input name
Name of the digital input for monitoring with elproMONITOR and for easy identification in the reports. The digital input must be provided with a unique name.Digital input status
This is an information field that reflects the current state (Enabled / Disabled) of the digital input. This field cannot be changed. The digital input is activated / deactivated in the monitor manually or automatically during a calibration.
Connection:
I/O module
Selection list with the available I/O modules. The digital input must be assigned to one of these I/O modules.I/O module channel
Selection list with all channels available at this I/O module. The digital input must be connected to one of these channels to receive its measured values. Only the channels that are still free are listed.
Info |
---|
Each digital input of an ECOLOG-4DI contains 3 channels:
For more information see >> digital input profiles |
Associated digital output
Selection list with the names of the available digital outputs. The digital input directly activates a digital output in case of an error. (e.g. of an ECOLOG-PRO 4DO).
Info |
---|
The parameterized internal contacts of ECOLOG-NET loggers (Alarm 1 and Alarm 2) cannot be controlled by elproMONITOR. |
Recording:
Recording interval
During a restart, the 1st measured value is recorded when the first full interval is reached.
The recording of the data is synchronous. All measured values and statuses are recorded simultaneously. The interval can be specified individually for each digital input. The intervals 1, 2, 3, 4 , 5, 6, 10, 12, 15, 20, 30 and 60 minutes are possible.
To correct the interval of an existing digital input, it must be deleted or decommissioned and then added again.
Note |
---|
The recording interval cannot be changed subsequently. |
Note |
---|
The two channels of ECOLOG-PRO 1THR and 2TH are interleaved. Once one of them has been defined, no other recording interval can be selected for the other one. |
Time control profile
With a >> time control profile, the digital input can be controlled time-dependently for monitoring by elproMONITOR. An already defined profile can be selected from this selection list.
Description:
Digital input ID
In addition to the digital input name, serves as a further parameter for identifying the digital input.Digital input note
Text field for entering input-related information.
Profile Set A and Profile Set B:
The profile sets are used to assign the following >> profiles.
Profile for alarms of digital inputs.
Profile for receiver in case of alarms
Info |
---|
With >> Time control profiles, it is possible to switch between Set A (default) and Set B. This is used to switch between different alarms and the corresponding receiver groups. |
List of existing sensor groups to which the digital input can be added or from which it can be removed.
Info |
---|
The digital input must be assigned to at least one sensor group by clicking the "Add" button. |
Info |
---|
Digital inputs can also be assigned to several sensor groups, which are displayed under "Sensor group name". |
Anchor | ||||
---|---|---|---|---|
|
The digital outputs overview is opened by clicking on the "Digital outputs" menu item in the Settings menu.
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
General:
Digital output Name
Name of the digital output for monitoring with elproMONITOR and for easy identification in the reports. The digital output must be provided with a unique name.I/O module
Selection list with the available I/O modules. The digital output must be assigned to one of these I/O modules. ECOLOG-PRO I/O modules or the Alarm Interface LAN can be used as I/O modules.I/O module channel
Selection list with all channels available at this I/O module. The digital output must be connected to one of these channels to receive its measured values. Only the channels that are still free are listed.Digital output ID
Serves as further parameter for identification besides the name of the digital output module. This ID is assigned by ELPRO during production of the module.Switch on test / Switch off test - test functions for the digital output.
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
General:
Sensor Group Name
Name of the sensor Group for monitoring a group of sensors easily with elproMONITOR. The sensor group must be provided with a unique name.
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
I/O Module:
I/O Module Name
Name of the I/O Module for monitoring with elproMONITOR and for easy identification in the reports. The I/O module must be provided with a unique name.Memo
In this area, information such as location of the I/O Module or the data loggers connected to the I/O moidule can be added.I/O Module Type
The type of the I/O Module can be selected from the drop down menu
I/O Module Type - Alarm Interface Ethernet - Obsolet
IP Address
Fixed IP address. The network administrator must assign the address to avoid network conflicts.Port Number
2101I/O Module ID
ID of the I/O Module that, the Alarm Interface Ethernet is usingPing
This command checks the network settings of the I/O module and the network connection. The test is ended by an OK or NOK confirmation
I/O Module Type - Alarm Interface USB - Obsolet
COM Port
COM Port that the USB is connectedI/O Module ID
ID of the I/O Module that, the Alarm Interface USB is usingPing
This command checks the network settings of the I/O module and the network connection. The test is ended by an OK or NOK confirmation
I/O Module ECOLOG-NET LP4, LH2, LA8, LR8,
IP Address
Fixed IP address. The network administrator must assign the address to avoid network conflicts.Port Number
2101Ping
This command checks the network settings of the I/O module and the network connection. The test is ended by an OK or NOK confirmation
I/O Module ECOLOG-PRO LBR
I/O Module ID
ID of the I/O Module that, the ECOLOG-PRO LBR is usingIP Address / Hostname
Fixed IP address / Hostname. The network administrator must assign the address to avoid network conflicts.Ping
This command checks the network settings of the I/O module and the network connection. The test is ended by an OK or NOK confirmationScan Bridge
Scans the I/O Modules that is using the ECOLOG-PRO LBR as network bridgeI/O Module detected
Check and adapt the settings of the I/O modules
I/O Module removed
Before saving, check whether the module configuration of the LBR in the elproMONITOR matches the hardware installation.
Removing an I/O module by saving the parameters without removing the sensors will result in the configuration data being lost.
The measured values will still be recorded, but after a restart raw milliamper values will be shown instead of - for instance - Celsius/Fahrenheit or relative humidity values.
I/O Module ECOLOG-PRO 1NTR
I/O Module ID
ID of the I/O Module that, the ECOLOG-PRO 1NTRRBR ID
ID of the ECOLOG-PRO RBR that the ECOLOG-PRO 1NTR is paired withNetwork ID
Identification of the elproMONITOR serverActual Signal to Noise Ratio (SNR)
Shows the Signal to Noise ration of the Radio connectionID: ECOLOG-PRO 1NTR
Unit can be edited from the Sensor Settings section
I/O Module ECOLOG-PRO 2PTR
I/O Module ID
ID of the I/O Module that, the ECOLOG-PRO 2PTRRBR ID
ID of the ECOLOG-PRO RBR that the ECOLOG-PRO 2PTR is paired withNetwork ID
Identification of the elproMONITOR serverActual Signal to Noise Ratio (SNR)
Shows the Signal to Noise ration of the Radio connectionID: ECOLOG-PRO 2PTR
Unit can be edited from the Sensor Settings section
I/O Module ECOLOG-PRO 1TRH
I/O Module ID
ID of the I/O Module that, the ECOLOG-PRO 1TRHRBR ID
ID of the ECOLOG-PRO RBR that the ECOLOG-PRO 1TRH is paired withNetwork ID
Identification of the elproMONITOR serverActual Signal to Noise Ratio (SNR)
Shows the Signal to Noise ration of the Radio connectionID: ECOLOG-PRO 1TRH
Temperature unit can be edited from the Sensor Settings section
Humudity Unit can be selected from the dropdown menu
I/O Module Lighthouse Particle Counter
IP Address
Fixed IP address. The network administrator must assign the address to avoid network conflicts.Port Number
502I/O Module ID
ID of the Particle CounterFlowrate, Preset at the Particle Counter Configuration
Product Name
Preset at the Particle Counter ConfigurationModel Name
Preset at the Particle Counter ConfigurationID:
Preset at the Particle Counter Configuration
Anchor | ||||
---|---|---|---|---|
|
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Sensor Limit Profile:
Sensor Limit Profile Name
Name of the Sensor Limit Profile for monitoring with elproMONITOR and for easy identification in the reports. The Snesor Limit Profile must be provided with a unique name.Lower Limit
In this area, the lower limit value which is not considered as deviation can be entered.Lower calculated limit
Calculated Limit is for setting a relation with Humudity Limit based on different temparatures. If customer wants to set up variying humudity limits based on temparature, here it is possible to set the equvation to calculate variying humudity limits changing with temperature value.Lower Limit Delay
Number of intervals that the Lower Limit value should be exceeded before elproMONITOR informs user about the deviation can be entered hereUpper Limit
In this area, the upper limit value which is not considered as deviation can be enteredUpper Calculated Limit
Calculated Limit is for setting a relation with Humudity Limit based on different temparatures. If customer wants to set up variying humudity limits based on temparature, here it is possible to set the equvation to calculate variying humudity limits changing with temperature value.Upper Limit Delay
Number of intervals that the Upper Limit value should be exceeded before elproMONITOR informs user about the deviation can be entered hereConsider logging intervals…
Entering a tick causes invalid values (no connection, sensor failure) to be taken into consideration as a violation of the alarm
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Sensor Issue Profile:
Sensor Issue Profile Name
Name of the Sensor Issue Profile for monitoring with elproMONITOR and for easy identification in the reports. The Sensor Issue Profile must be provided with a unique name.No Connection Alarm
The alarm is activated only by ticking the hook.No Connection Delay
Number of intervals that the No Connection Failure should occure before elproMONITOR informs user about the issue can be entered hereSensor Failure
The issue is activated only by ticking the hook.Sensor Failure Delay
Number of intervals that the Sensor Failure should occure before elproMONITOR activates the deviation, can be entered hereLow Battery Notification
The issue is activated only by ticking the hook.Radio Strenght Warning
The issue is activated only by ticking the hook.Radio Strenght Warning Delay
Number of intervals that the poor radio strenght should occure before elproMONITOR activates the deviation, can be entered hereSignal to Noise Ratio Threshold
The user defined value to set the custom radio streng; taking in to account the ratio between, signal and noise level.One of the following options should be selected to set the alarm level for radio strenght
Weak Radio Strenght
Bad Radio Strenght
Custom Radio Strenght
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Digital Input Profile:
Digital Input Profile Name
Name of the Digital Input Profile for monitoring with elproMONITOR and for easy identification in the reports. The Digital Input Profile must be provided with a unique name.I/O Module Type
Here the correct I/O Module type can be selected. Options are ECOLOG-PRO 4DI or ECOLOG-NETMode
Here the Log mode can be selected, there following options availableSTANDARD The status at the moment when the interval was started is shown by the Digital Input
TIME MONITORING The duration of the contact status (open, closed) as a percentage of the logging interval is used as the activation is shown by the Digital Input (min. 200 ms)
EDGE COUNTER The number of contact status changes (rising, falling) per logging interval is used as the activationmis shown by the Digital Input (min. 200 ms)
Text if Input=1 or 0
Text field for entering the message textLogic
Alarm if Input = 1 Alarms if the Digtial Input Status changes from 0 to 1
Alarm if Input = 0 Alarms if the Digital Input Status changes from 1 to 0Delay
Delay time, enter in logging interval steps
Mode Time Monitor:
Border greater than, Border less than
Limit values in % of the logging interval.Text if outer Border, Text if inner Border
Text field for entering the message text
Mode Edge Counter:
Border Greater Than, Border less than
Limit values in number of edge changes.Text if outside limits, Text if inside limits
Text field for entering the message text.
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Create New Recipient Profile:
Recipient Profile Name
Name of the Recipient Profile for monitoring with elproMONITOR and for easy assigning of the recipients. The Recipient Profile must be provided with a unique name.E-Mail
The e-mail alarm is activated by ticking the checkbox. All information needed to identify an issue is automatically contained in the e-mail
To, Cc, Subject: This information is used to address the e-mail.
Text This field should contain information such as process information, responsibilities, and instructions, and is attached to each e-mail. Relevant Information can be added by selecting from the menu on the right side of the Text field. As default all informations are selectedSend Test E-Mail is to test the functions
Aggregated Alarm Email:
This option is used to receive a summary of the active and/or inactive deviations in a specific time period as an e-mail. This means the sensor must be configured accordingly in order to obtain a deviation
The aggregated email alarm is activated by ticking the checkbox
Aggregation Interval of Change
Interval time as minutes can be selected from the drop down menuTo, Cc, Subject: This information is used to address the e-mail.
Text This field should contain information such as process information, responsibilities, and instructions, and is attached to each e-mail. Relevant Information can be added by selecting from the menu on the right side of the Text field. As default all informations are selectedSend Test Aggregated E-Mail is to test the functions
SMS:
The SMS alarm is activated by ticking the checkbox
SMS Number
The mobile phone number that elproMONITOR should send the alarm information to.SMS Text
This field should contain information such as process information, responsibilities, and instructions, and is attached to each SMS. Relevant Information can be added by selecting from the menu on the right side of the Text field. As default all informations are selectedSend Test SMS is to test the functions
Digital Outputs:
Digital Output 1, Digital Output 2
Selection list of configured digital outputs.Plugin
Plugin, Parameters: This is a customer-specific software module. It is produced by Elpro-Buchs AGTest Plugin is to test the functions
Repeat Notification:
The Repeat Notification is activated by ticking the checkbox
Repeat Notification Integral
The interval time in minutes can be input here
Anchor | ||||
---|---|---|---|---|
|
The scheduler is used to provide a day time-dependent control over the warning and alarm functions of elproMONITOR. For each sensor or digital input it is possible to define a schedule which switches between several alarm profiles. There are 2 alarm profiles (SET A, SET B) and a deactivation option. The defined profiles are assigned to the sensors and digital inputs with CREATE/EDIT NEW SENSOR or CREATE/EDIT NEW DIGITAL INPUT
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Create New Schedule Profile:
Schedule Profile Name
Name of the Schedule Profile for monitoring with elproMONITOR. The Schedule Profile must be provided with a unique name.By Day Time (…)
To change the state of a particular field, highlight it with the mouse pointer and change the state by clicking on the corresponding button. It is not possible to change the time grid resolutionExample
SET A - Weekdays (Green)
SET B - Weekends (Purple)
DEACTIVATED - Deactivated days (Yellow)
CLEAR - The entire profile is overwritten by SET A
Selected: Wed 04:30 - 05.0 am
By Date
Specify the alarm period by entering the calendar day and the alarm profileAdd New
Add a new calendar day and profileRemove
Deletes the inputBy Digital Inputs
Profile Set B by Digital Input - The selected digital input switches between alarm profiles SET A and SET B.
Deactivated by Digital Input -The selected digital input deactivates all the alarm functions controlled by this profile.
Anchor | ||||
---|---|---|---|---|
|
The target directory for exporting data from elproMONITOR is defined in this profile
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Create New Destination Profile:
Data Destination Profile Name
Name of the Data Destination Profile for saving monitoring data with elproMONITOR. The Data Destination Profile must be provided with a unique name.Connection Test
Function to test the data export. The test is ended by an OK or NOK confirmation
Data Destination:
Type
FTP - The exported data are saved on a FTP server. Only passive FTP is currently supported.
NETDRIVE - The exported data are saved on a network drive. • Path Directory on a network drive (e.g.: \\192.168.100.20\DataExport)
DRIVE - The exported data are saved locallyPath
Directory on the server incl. server address (z.B.: ftp:// meinserver.com/export)
Directory on a network drive (e.g.: \\192.168.100.20\DataExport)
Local drive and directory (e.g.: C:\export)Login name, password
Login information for this server
The domain or IP address of the target computer must always be before the login name (e.g. DOMAIN\Username or 192.168.100.20\Username)
Anchor | ||||
---|---|---|---|---|
|
The subfolder used for saving, the name and content of the exported file are defined in this profile.
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Create New Data Export Profile:
Data Export Profile Name
Name of the Data Export Profile for saving monitoring data with elproMONITOR. The Data Export Profile must be provided with a unique name.Output-Format
By setting the tick, the corresponding output formats are activated
CSV - The export takes place as a CSV file
PDF - The export takes place as a PDF file
One PDF containing all sensors - A PDF file with all sensors will be created. The first page of the PDF document contains the overlay of all sensorsTimeZone
Time zone that the data export will be done, can be selected from the drop down menu
Adjust for Daylight Savings Time - if ticked, elproMONITOR will adjust the daylight saving automatically
File-Description
Subfolder - Subfolder options can be selected by left click on them. Left arrow will carry the selected option to Subfolder area and relevant data will be exported. Order in the Subfolder area can be adjusted by up and down arrows.
A selected Subfolder option can be deselected by carrying it back to Subfolder options area by right arrow.Prefix for Filename - Text field for entering the chosen prefix
Filename - File name defined from the file options and order of the file options can be adjusted the same way as described in Subfolder section
Overwrite existing files - Entering a tick in the checkbox means that an existing file is overwritten by a new file with the same designation
CSV-Configuration
CSV-Token - CSV-Token options can be selected by left click on them. Left arrow will carry the selected option to CSV-Token area and relevant data will be exported. Order in the CSV-Token area can be adjusted by up and down arrows.
A selected CSV-Token option can be deselected by carrying it back to CSV-token options area by right arrow.Dateformat
Dateformat can be selected from the dropdown menu. Date format can be selected either purely numeric format or Month is abbreviatedTimeformat
It is possible to select that the time be displayed in either a 12 hour or 24 hour time formatDecimaldescriptor
The decimal can be shown as a point or commaCSV-Separator
It is possible to select either a semi-colon or comma. If a comma is selected as a decimal separator, the comma cannot be used as a CSV-separator
Anchor | ||||
---|---|---|---|---|
|
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Create New Export Schedule Task:
Export Schedule Task Name
Name of the Export Schedule Task for saving monitoring data with elproMONITOR. The Export Schedule Task must be provided with a unique name.Data Export Profile
Allocation of a data export profileData Destination Profile
Allocation of a data destination profileRecipient Profile
Assignment of the recipientCreate Testfile / Send Testfile
Tests the function for the seleckted profiles
Interval
The time span between two exports can be selected: hourly, daily, weekly or monthly. At the beginning of the new interval plus a possible data safety clearance, the report is created over the last interval. The beginning and the end of the time window can not be changed. For example, for a monthly interval, it is not possible to choose the time window from mid-month 1 to mid-month 2; It is always from the beginning to the end of the monthData Safety Clearance
The time of data export is delayed by the Data Safety Clearance to allow reloading of non-directly transmitted values (e.g., due to a connection break to the measurement modules)
For example, if a 3-day Data Safety Clearance is set for a scheduled monthly export, the automatic export does not start in the early morning of the first day of a month for the previous month, but 3 days later, this means in the early morning of the 4th day of the new month. Thus, missing values of the previous month can be reloaded during these three days and would thus also be included in the export.Unit
Depending on the selected interval, the unit for the Data Safety Clearance is hours, days or months
Sensors
By selecting the sensor from the dropdown menu and adding it, the sensors for the report are definedSensor Name
Selected sensors are listed hereRemove - Removes the Sensir from the list
Digital Inputs
By selecting the Digital Input from the dropdown menu and adding it, the Digital Input for the report are definedDigital Input Name
Selected Digital Inputs are listed hereRemove - Removes the Digital Input from the list
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Create New Comment Template:
Comment Template Name
Name of the Comment Template for saving comments with elproMONITOR. The Comment Template must be provided with a unique name.Text
Text assigned to the Comment TemplateAllow Edit
If ticked comment text can be edite
Anchor | ||||
---|---|---|---|---|
|
These are the settings for E-Mail server
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
II - E-Mail Server Settings
E-Mail:
E-Mail Server Type
E-Mail Server type can be selected from dropdown menuE-Mail Server (SMTP) or (Microsift Office 365)
Required Host or IP for SMTP Server or Tenand, Cliend IDs for Microsift Office 365 Server can be input hereServer Requires Authentication
If ticked User name and Password can be input hereTest connection
Function for testing the e-mail connection between the elproMONITOR software and the email server. The test is ended by an OK or NO
Sender
Name - Name of the elproMONITOR platformE-Mail - email of the sender
Send Queue
This function repeats e-mail transmission until the e-mail is sent successfully. The queue of pending messages is cleared by deactivating this function.
• Repeat Time Interval Delay time between repeated e-mails.
• Maximum Queue Time Maximum time to send the e-mail repeatedlyKeep Alive E-Mail
This function is used to send a check e-mail at regular intervals. This ensures that the notification works in case of alarm.
• Maximal Time between Messages - Delay time between Keep Alive E-Mails.
• Message Send Time - Time when the Keep Alive E-Mail is sent.
• Recipient Profiles - Please refer to Recipient Profile section
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
II - E-Mail Server Settings
SMS:
USB
- COM port
- Baud Rate (Standard 57600)
- SIM Card PIN CodeTest Signal Strength
Function for testing the SMS connection between the elproMONITOR software and the SMS server. The test is ended by an OK or NOK confirmation.
SMS:
Ethernet
- IP Address
- Port Number (Standard 10001)
- SIM Card PIN CodeTest Signal Strength
Function for testing the SMS connection between the elproMONITOR software and the SMS server. The test is ended by an OK or NOK confirmation.
Send Queue
This function repeats SMS transmission until the SMS is sent successfully. The queue of pending messages is cleared by deactivating this function.
Repeat Time Interval - Delay time between the repeated SMS.
Maximum Queue Time - Maximum time to send the SMS repeatedlyKeep Alive SMS
This function is used to send a check SMS at regular intervals. This ensures that the notification works in case of alarm.
Maximal Time between Messages - Delay time between Keep Alive SMS Texts
Message Send Time - Time when the Keep Alive SMS is sent.
Recipient Profile - Please refer to the Recipient Profile Section
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
II - System Issues
System Issues:
Recipient Profile
The Recipient Profile for forwarding the Issue message can be selected from the dropdown menu
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
II - Licenses Page
License:
One license is used for each sensor and digital input. The license continues to be assigned for a sensor in Retired state, i.e. which only exists to display historical data. When a sensor is added, a check is made whether there is a free license. Deleting a sensor will not result in a refund of fees. However, the assigned license is released and can be used for a new sensor.
License Order
Step 1 - The customer requires additional sensor licenses and inputs the required amount to Requested number of licenses field and clicks Create License Order.
Step 2 - Customer sends the created order to Elpro Buchs AG.Upload License
Step 1 - Customer receives a License file from Elpro Buchs AG.
Step 2 - Customer Uploads the received file to elproMONITOR. Upload activates the new licenses
Anchor | ||||
---|---|---|---|---|
|
Anchor | ||||
---|---|---|---|---|
|
Drawio | ||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
II - Profile
Profile:
The Profile function is used to edit user-specific defaults.
Language - At present the software is only available in German and English.
Display Time Zone (only applies to current user) - Defines the time zone used for the display.
Adjust for Daylight Saving Time - Tick the checkbox to adjust between summer and winter time automatically.
Show Retired Sensors - "Retired" sensors can only be shown for this user in all views by ticking this checkbox.