elproMONITOR / Settings (EN)

Information

Important information and warnings

DELETE

Windows function, e.g. Delete

<xxxxxx>

Syntax for placeholders.
Placeholders are written between < > characters.

>>

Reference to a further chapter or document.

The representation refers only to a part of the user interface.

In the interest of our clientele, we reserve the right to make changes due to technical advances. Therefore, schematics, descriptions and scope of delivery may be changed without prior notice. This manual is valid as of version 2017.

Liability

  • In no event shall ELPRO-BUCHS AG be liable for any direct, indirect, special, incidental, consequential or punitive damages or losses, including lost profits and data, arising out of the use of your data loggers, sensors, accessories, software products or the information contained in the documentation.

  • ELPRO-BUCHS AG does not bear any responsibility for the installation of the software products.

  • ELPRO-BUCHS AG makes no warranties of any kind, express or implied, regarding the merchantability and fitness of your products for any particular purpose.

  • In the interest of our clientele, we reserve the right to make changes and discontinuations due to technical advances. Therefore functionality, schemes, descriptions and scope of delivery can be changed without prior notice!

  • Because some countries or states do not allow the limitation of the term implied warranty or disclaimer of incidental or consequential damages, the limitations and exclusions may not apply to every purchaser. If any provision of this warranty is held invalid or unenforceable by a court of competent jurisdiction, it will not affect the validity or enforceability of the remaining provisions.

  • ELPRO-BUCHS AG accepts no liability for transport damage or any consequential damage resulting therefrom.

  • In general, the legal provisions of Switzerland apply. The place of jurisdiction is the district court of Werdenberg-Sarganserland.

Warranty

  • The warranty obligations are limited, at ELPRO-BUCHS AG's discretion, to the repair, refund of the purchase price, repair free of charge or replacement of a defective product returned to ELPRO-BUCHS AG or a reseller approved by ELPRO-BUCHS AG within the warranty period.

  • There is no entitlement to free "on-site customer support" by an employee of ELPRO-BUCHS AG.

  • The warranty extends only to the original purchaser or end user and customers of a reseller authorized by ELPRO-BUCHS AG.

  • Resellers approved by ELPRO-BUCHS AG are not authorized to provide a greater or other warranty on behalf of ELPROBUCHS AG.

  • ELPRO-BUCHS AG grants a warranty period of 24 months on the following new products:

    • Data logger

    • Brackets

    • Accessories, except sensors and third-party products

  • This warranty applies to material defects or production defects.

  • ELPRO-BUCHS AG grants a warranty period of 6 months for the following products and services:

    • All service work and repairs

    • Temperature sensors

    • Humidity sensors

  • ELPRO-BUCHS AG grants a warranty period of 90 days that the medium on which the software product was delivered is free from defects in material and workmanship under normal conditions. The software product conforms in all material respects to the operating instructions and the information in the help file.

  • The warranty does not apply to consumables, disposable batteries or any other product which, in the opinion of ELPRO-BUCHS Ltd:

    • abused

    • changed

    • replaced by a wrong product

    • has been operated and damaged outside the specification due to accident or operating or handling conditions.

  • Wear and tear, cable breakage and corrosion cannot be claimed under warranty.

  • For third-party products, ELPRO-BUCHS AG grants at most the warranty period of the manufacturer.

  • For discontinued products, ELPRO-BUCHS AG provides warranty work and customer support only for a limited period of time.

  • Warranty repairs are generally only carried out at the factory (ELPRO-BUCHS AG) or at an agency recognized by the factory.

  • ELPRO-BUCHS AG does not provide any warranty regarding the standard or SCS calibration of the data loggers and sensors. The specified data correspond to the situation during the calibration process

Software

  • The software products of ELPRO-BUCHS AG are subject to internal quality regulations and are regularly validated within the factory. In the event of any program errors, bypassing the error is considered as elimination.

  • Software operating instructions do not contain instructions on the basic operation of a computer or on basic functions of the Windows® operating system. For information on how to operate your computer or operating system, please refer to the appropriate manuals for your computer.

Data loggers, sensors and accessories

  • ELPRO-BUCHS AG uses the highest quality standards and a certified quality management system according to ISO 9001 for the production of data loggers and their accessories.

  • For information on the operation of the data loggers and their accessories, please refer to the corresponding product documentation provided by ELPRO-BUCHS AG.

  • When installing data loggers, sensors and accessories, the locally applicable installation regulations must be observed.

  • For applications in potentially explosive atmospheres, the zone assignment specified by ELPRO-BUCHS AG as well as the application and safety instructions must be strictly observed.

  • In the event of a warranty claim, the customer will receive a repair cost estimate from ELPRO-BUCHS AG in order to issue the appropriate authorization before work commences.

  • The transport costs for a repair at ELPRO-BUCHS AG will be borne by the customer. DAP (value added tax) will be borne by ELPROBUCHS AG.

  • ELPRO-BUCHS AG reserves the right to charge the purchaser for costs of repairs/parts replacement.

  • After repair, the product will be returned to the buyer with return shipping charges billed to the buyer (FOB shipping location).

Trademark

  • All listed company and product names and their trademarks are the protected property of their respective owners.

  • This product is subject to CE marking.

  • The manufacturer guarantees the conformity of this product to the corresponding directives: EN 61000-6-2 : 2001 and EN 61000-6-4 : 2001

  • FCC ID: Z45-E11645398

  • IC: 9954A-E11645398

  • This product must be disposed of in accordance with WEEE (Waste electrical and electronic equipment, 2002/ 96/EC)!


1. Overview Settings

In the SETTINGS, the parameters are specified which the elproMONITOR software uses for the current monitoring task. These parameters contain settings for

  • >> Device settings - Here all I/O modules for ECOLOG-PRO, ECOLOG-NET and the alarm interface as well as associated digital inputs, digital outputs, sensors and sensor groups are parameterized.

  • >> Profiles - All profiles for sensor limits (alarms, warnings), sensor faults, digital input profiles, receiver profiles, time control profiles, data destimation profiles and data export profiles are managed here.

  • >> Program - This is where scheduled exports, comment templates, e-mail recipient lists, SMS, system malfunctions and licenses are parameterized and managed.

  • >> User - Here you can make settings for your own user profile.

1.1. User Interface

The Settings overview is opened by clicking on the "Settings" menu item. The default view is the existing >> sensors of the >> device settings.

A - Details

A left click on a specific line opens the detail view for this setting. The detail view includes a list of all objects from the previous menu (here sensors) and the details of the selected object (here freezer temperature 1). No changes can be made directly in the details, but it is possible to switch between the individual objects by making the appropriate selection with the mouse in the details view. (see 1 in the graphic)

I - Devices Settings

The individual device settings can be parameterized in this area:

  • >> 2. Sensors

  • >> 3. Digital inputs

  • >> 4. Digital outputs

  • >> 5. Sensor groups

  • >> 6. I/O modules

II - Profiles

Profiles contain specifications for specific information that can be assigned to the devices:

  • >> Sensor limit profiles

  • >> Profiles for sensor malfunctions

  • >> Digital input profile

  • >> Receiver profiles

  • >> Time control profiles

  • >> Data destination profiles

  • >> Data export profiles

III - Apptication Settings

In the program settings, device-independent parameterizations of the software are made:

  • >> Export Schedule Tasks

  • >> Comment Templates

  • >> E-Mail

  • >> SMS

  • >> System Issues

  • >> License

IV - User Settings

User settings can be made specific to each user:

  • >> Profile

V - Detail Column

 

This area contains all information about the settings in the selected area. Different information is available for each setting and is described in the following chapters

VI - Applicable Functions

Depending on the selected overview, different functionalities can be executed here which are specifically described in the following chapters.

2. Sensors

The Sensors overview is opened by clicking on the "Sensors" menu item in the Settings menu.

A - Details

With a left click on a certain line the detail view Sensors opens. The detailed view includes a list of all objects from the Sensors overview and the details of the selected object (here Freezer Temperature 1). The applicable functions for the selected sensor are described in III - Applicable functions and are:

  • Report

  • Add new sensor

  • Retire

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable Functions)

  • Edit

  • Retire

  • Delete

I - Devices Settings

The Sensors overview is opened by clicking on the "Sensors" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the sensors. The following information is available for each sensor:

  • Sensor - name of the sensor

  • I/O Module - name of the I/O module >> I/O Module

III - Applicable Functions

The following functionalities can be executed here.

Report

A >> elproMONITOR configuration report with all selected parameters is created.

Add new sensor

The details in the view are replaced by the following parameters for creating a new sensor:

 

 

 

 

General:

  • Sensor name
    Name of the sensor for monitoring with elproMONITOR and for easy identification in the reports. The sensor must be provided with a unique name.

  • Sensor status
    This is an information field that reflects the current state (Enabled / Disabled) of the sensor. This field cannot be changed. The sensor is activated / deactivated in the monitor manually or automatically during a calibration.

 

Connection:

  • I/O module
    Selection list with the available I/O modules. The sensor must be assigned to one of these I/O modules.

  • I/O module channel
    Selection list with all channels available at this I/O module. The sensor must be connected to one of these channels to receive its measured values. Only the channels that are still free are listed.

  • Associated digital output
    Selection list with the names of the available digital outputs. The sensor activates a digital output directly in the event of an error. (e.g. of an ECOLOG-PRO 4DO).

 

Recording:

  • Recording interval
    At a restart, the 1st measured value is recorded when the first full interval is reached.
    The recording of the data is synchronous. All measured values and statuses are recorded simultaneously. The interval can be specified individually for each sensor. The intervals 1, 2, 3, 4 , 5, 6, 10, 12, 15, 20, 30 and 60 minutes are possible.
    To correct the interval of an existing sensor, it must be deleted or decommissioned and then added again.

  • Time control profile
    With a >> time control profile, the sensor can be controlled time-dependently for monitoring by elproMONITOR. An already defined profile can be selected from this selection list.

 

Description:

  • Sensor ID
    In addition to the sensor name, serves as a further parameter for identifying the sensor.

  • Sensor note
    Text field for entering sensor-related information.

 

Profile Set A and Profile Set B:

The profile sets are used to assign the following >> profiles.

  • Profile for alarms due to limit violations.

  • Profile for receiver in case of alarms

  • Profile for warnings due to limit violations.

  • Profile for receiver in case of warnings

  • Profiles for sensor malfunctions

  • Profiles for receivers in the event of sensor malfunctions.

 

 

List of existing sensor groups to which the sensor can be added or from which it can be removed.

Retire

Opens the window for permanently retiring the selected sensor. No further data will be recorded. Retiring is only possible after selecting a comment template or entering a comment and authentication with the password.

Delete

Opens the window for permanently deleting the selected sensor. No further data will be recorded. Deletion is possible only after selecting a comment template or entering a comment and authentication with the password.

Edit

The same parameters as in >> Add new sensor are displayed for editing.

Close

Closes the current window and returns to the Sensors overview.

3. Digital Inputs

The digital inputs overview is opened by clicking on the "Digital inputs" menu item in the Settings menu.

A - Details

With a left click on a certain line the detail view digital inputs opens. The detailed view includes a list of all objects from the digital inputs overview and the details of the selected object (here Door Contact 1). The applicable functions for the selected digital input are described in III - Applicable functions and are:

  • Report

  • Add new digital input

  • Shutdown

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Shutdown

  • Delete

I - Devices Settings

The digital inputs overview is opened by clicking on the "Digital inputs" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the digital inputs. The following information is available for each digital input:

  • Digital input name - name of the digital input

  • I/O Module - name of the I/O module >> I/O Module

III - Applicable Functions

The following functionalities can be executed here.

Report

A >> elproMONITOR configuration report with all selected parameters is created.

Add new digital input

The details in the view are replaced by the following parameters for creating a new digital input:

 

 

General:

  • Digital input name
    Name of the digital input for monitoring with elproMONITOR and for easy identification in the reports. The digital input must be provided with a unique name.

  • Digital input status
    This is an information field that reflects the current state (Enabled / Disabled) of the digital input. This field cannot be changed. The digital input is activated / deactivated in the monitor manually or automatically during a calibration.

 

 

Connection:

  • I/O module
    Selection list with the available I/O modules. The digital input must be assigned to one of these I/O modules.

  • I/O module channel
    Selection list with all channels available at this I/O module. The digital input must be connected to one of these channels to receive its measured values. Only the channels that are still free are listed.

  • Associated digital output
    Selection list with the names of the available digital outputs. The digital input directly activates a digital output in case of an error. (e.g. of an ECOLOG-PRO 4DO).

 

 

Recording:

  • Recording interval
    During a restart, the 1st measured value is recorded when the first full interval is reached.
    The recording of the data is synchronous. All measured values and statuses are recorded simultaneously. The interval can be specified individually for each digital input. The intervals 1, 2, 3, 4 , 5, 6, 10, 12, 15, 20, 30 and 60 minutes are possible.
    To correct the interval of an existing digital input, it must be deleted or decommissioned and then added again.

  • Time control profile
    With a >> time control profile, the digital input can be controlled time-dependently for monitoring by elproMONITOR. An already defined profile can be selected from this selection list.

 

 

Description:

  • Digital input ID
    In addition to the digital input name, serves as a further parameter for identifying the digital input.

  • Digital input note
    Text field for entering input-related information.

 

 

Profile Set A and Profile Set B:

The profile sets are used to assign the following >> profiles.

  • Profile for alarms of digital inputs.

  • Profile for receiver in case of alarms

 

 

List of existing sensor groups to which the digital input can be added or from which it can be removed.

Retire

Opens the window for permanently retiring the selected digital input. No further data will be recorded. The retire is only possible after selecting a comment template or entering a comment and authentication with the password.

Delete

Opens the window for permanently deleting the selected digital input. No further data will be recorded. Deletion is possible only after selecting a comment template or entering a comment and authentication with the password.

Edit

The same parameters as in >> Add new digital input are displayed for editing.

Close

Closes the current window and returns to the Digital Inputs overview.

4. Digital Outputs

The digital outputs overview is opened by clicking on the "Digital outputs" menu item in the Settings menu.

A - Details

With a left click on a certain line the detail view digital outputs opens. The detailed view includes a list of all objects from the overview digital outputs and the details of the selected object (here Alarm Lights). The applicable functions for the selected digital output are described in III - Applicable functions and are:

  • Report

  • Add new digital output

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The digital outputs overview is opened by clicking on the "Digital outputs" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the digital outputs. The following information is available for each digital output:

  • Digital output name - name of the digital output

  • I/O Module - name of the I/O module >> I/O Module

  • Watchdog - the digital output has been configured as monitoring (in case of power failure or disconnected connection) for the corresponding module.

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Add new digital output

The details in the view are replaced by the following parameters for creating a new digital output:

 

 

General:

  • Digital output Name
    Name of the digital output for monitoring with elproMONITOR and for easy identification in the reports. The digital output must be provided with a unique name.

  • I/O module
    Selection list with the available I/O modules. The digital output must be assigned to one of these I/O modules. ECOLOG-PRO I/O modules or the Alarm Interface LAN can be used as I/O modules.

  • I/O module channel
    Selection list with all channels available at this I/O module. The digital output must be connected to one of these channels to receive its measured values. Only the channels that are still free are listed.

  • Digital output ID
    Serves as further parameter for identification besides the name of the digital output module. This ID is assigned by ELPRO during production of the module.

  • Switch on test / Switch off test - test functions for the digital output.

Delete

Opens the window for permanently deleting the selected digital output. No further data will be recorded. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add new digital output are displayed for editing.

Close

Closes the current window and returns to the Digital Outputs overview.

5. Sensor Group

 

A - Details

With a left click on a certain line the detail view sensor group opens. The detailed view includes a list of all sensors from the overview sensor group and the details of the selected object (Sensor Group name). The applicable functions for the selected sensor groups are described in III - Applicable functions and are:

  • Report

  • Add new Sensor Group

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The Sensor Group overview is opened by clicking on the "Sensor Groups" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the sensor group The following information is available for each sensor group:

  • Sensor Group name - name of the sensor group

III - Applicable Functions

The following functionalities can be executed here.

Report

A >> elproMONITOR configuration report with all selected parameters is created.

Add new Sensor Group

The details in the view are replaced by the following parameters for creating a new sensor group:

 

 

General:

  • Sensor Group Name
    Name of the sensor Group for monitoring a group of sensors easily with elproMONITOR. The sensor group must be provided with a unique name.

Delete

Opens the window for permanently deleting the selected sensor group. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add new sensor group are displayed for editing.

Close

Close appears in Details section and closes the current window and returns to the Sensor Group overview.

6. I/O Modules

A - Details

With a left click on a certain line the detail view I/O Module opens. The detailed view includes a list of all I/O Modules from the overview I/O Modules and the details of the selected object. The applicable functions for the selected I/O Modules are described in III - Applicable functions and are:

  • Report

  • Add new digital output

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The I/O Module overview is opened by clicking on the "I/O Modules" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the sensor group The following information is available for each I/O Module:

  • I/O Module name - name of the I/O Module

  • I/O Module Type - Type of the I/O module assigned to the chosen name

  • Changed - If a I/O Module configuration change took place, here a red dot appears to indicate the change.

III - Applicable Functions

The following functionalities can be executed here.

Report

A >> elproMONITOR configuration report with all selected parameters is created.

Add New I/O Module

The details in the view are replaced by the following parameters for creating a new I/O Module:

 

I/O Module:

  • I/O Module Name
    Name of the I/O Module for monitoring with elproMONITOR and for easy identification in the reports. The I/O module must be provided with a unique name.

  • Memo
    In this area, information such as location of the I/O Module or the data loggers connected to the I/O moidule can be added.

  • I/O Module Type
    The type of the I/O Module can be selected from the drop down menu

 

 

I/O Module Type - Alarm Interface Ethernet - Obsolet

  • IP Address
    Fixed IP address. The network administrator must assign the address to avoid network conflicts.

  • Port Number
    2101

  • I/O Module ID
    ID of the I/O Module that, the Alarm Interface Ethernet is using

  • Ping
    This command checks the network settings of the I/O module and the network connection. The test is ended by an OK or NOK confirmation

 

 

I/O Module Type - Alarm Interface USB - Obsolet

  • COM Port
    COM Port that the USB is connected

  • I/O Module ID
    ID of the I/O Module that, the Alarm Interface USB is using

  • Ping
    This command checks the network settings of the I/O module and the network connection. The test is ended by an OK or NOK confirmation

 

 

I/O Module ECOLOG-NET LP4, LH2, LA8, LR8,

  • IP Address
    Fixed IP address. The network administrator must assign the address to avoid network conflicts.

  • Port Number
    2101

  • Ping
    This command checks the network settings of the I/O module and the network connection. The test is ended by an OK or NOK confirmation

 

 

I/O Module ECOLOG-PRO LBR

  • I/O Module ID
    ID of the I/O Module that, the ECOLOG-PRO LBR is using

  • IP Address / Hostname
    Fixed IP address / Hostname. The network administrator must assign the address to avoid network conflicts.

  • Ping
    This command checks the network settings of the I/O module and the network connection. The test is ended by an OK or NOK confirmation

  • Scan Bridge
    Scans the I/O Modules that is using the ECOLOG-PRO LBR as network bridge

    • I/O Module detected

      • Check and adapt the settings of the I/O modules

    • I/O Module removed
      Before saving, check whether the module configuration of the LBR in the elproMONITOR matches the hardware installation.
      Removing an I/O module by saving the parameters without removing the sensors will result in the configuration data being lost.
      The measured values will still be recorded, but after a restart raw milliamper values will be shown instead of - for instance - Celsius/Fahrenheit or relative humidity values.

 

 

I/O Module ECOLOG-PRO 1NTR

  • I/O Module ID
    ID of the I/O Module that, the ECOLOG-PRO 1NTR

  • RBR ID
    ID of the ECOLOG-PRO RBR that the ECOLOG-PRO 1NTR is paired with

  • Network ID
    Identification of the elproMONITOR server

  • Actual Signal to Noise Ratio (SNR)
    Shows the Signal to Noise ration of the Radio connection

  • ID: ECOLOG-PRO 1NTR
    Unit can be edited from the Sensor Settings section

 

 

I/O Module ECOLOG-PRO 2PTR

  • I/O Module ID
    ID of the I/O Module that, the ECOLOG-PRO 2PTR

  • RBR ID
    ID of the ECOLOG-PRO RBR that the ECOLOG-PRO 2PTR is paired with

  • Network ID
    Identification of the elproMONITOR server

  • Actual Signal to Noise Ratio (SNR)
    Shows the Signal to Noise ration of the Radio connection

  • ID: ECOLOG-PRO 2PTR
    Unit can be edited from the Sensor Settings section

 

 

I/O Module ECOLOG-PRO 1TRH

  • I/O Module ID
    ID of the I/O Module that, the ECOLOG-PRO 1TRH

  • RBR ID
    ID of the ECOLOG-PRO RBR that the ECOLOG-PRO 1TRH is paired with

  • Network ID
    Identification of the elproMONITOR server

  • Actual Signal to Noise Ratio (SNR)
    Shows the Signal to Noise ration of the Radio connection

  • ID: ECOLOG-PRO 1TRH
    Temperature unit can be edited from the Sensor Settings section
    Humudity Unit can be selected from the dropdown menu

 

 

I/O Module Lighthouse Particle Counter

  • IP Address
    Fixed IP address. The network administrator must assign the address to avoid network conflicts.

  • Port Number
    502

  • I/O Module ID
    ID of the Particle Counter

  • Flowrate, Preset at the Particle Counter Configuration

  • Product Name
    Preset at the Particle Counter Configuration

  • Model Name
    Preset at the Particle Counter Configuration

  • ID:
    Preset at the Particle Counter Configuration

 

 

 

 

Delete

Opens the window for permanently deleting the selected I/O Module. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add New I/O Module are displayed for editing.

Close

Close appears in details section and closes the current window and returns to the I/O Modules overview.

Profiles

7. Sensor Limit Profiles

A - Details

With a left click on a certain line the detail view Sensor Limit Profile opens. The detailed view includes a list of all Sensor Limit Profiles from the overview Sensor Limit Profiles and the details of the selected object. The applicable functions for the selected Sensor Limit Profiles are described in III - Applicable functions and are:

  • Report

  • Add New Profile

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The Sensor Limit Profile is opened by clicking on the "Sensor Limit Profiles" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the Sensor Limit Profile. The following information is available for each Sensor Limit Profile:

  • Sensor Limit Profile Name - name of the Sensor Limit Profile

  • Lower Limit- The lower limit value for the sensor to be identified as a deviation when exceeded

  • Lower Limit Delay- Number of intervals that the Lower Limit value should be exceeded before elproMONITOR informs user about the deviation

  • Upper Limit- The upper limit value for the sensor to be identified as a deviation when exceeded

  • Upper Limit Delay- Number of intervals that the Upper Limit value should be exceeded before elproMONITOR informs user about the deviation

III - Applicable Functions

The following functionalities can be executed here.

Report

A >> elproMONITOR configuration report with all selected parameters is created.

Add New Profile

The details in the view are replaced by the following parameters for creating a new Sensor Limit Profile:

 

 

Sensor Limit Profile:

  • Sensor Limit Profile Name
    Name of the Sensor Limit Profile for monitoring with elproMONITOR and for easy identification in the reports. The Snesor Limit Profile must be provided with a unique name.

  • Lower Limit
    In this area, the lower limit value which is not considered as deviation can be entered.

  • Lower calculated limit
    Calculated Limit is for setting a relation with Humudity Limit based on different temparatures. If customer wants to set up variying humudity limits based on temparature, here it is possible to set the equvation to calculate variying humudity limits changing with temperature value.

  • Lower Limit Delay
    Number of intervals that the Lower Limit value should be exceeded before elproMONITOR informs user about the deviation can be entered here

  • Upper Limit
    In this area, the upper limit value which is not considered as deviation can be entered

  • Upper Calculated Limit
    Calculated Limit is for setting a relation with Humudity Limit based on different temparatures. If customer wants to set up variying humudity limits based on temparature, here it is possible to set the equvation to calculate variying humudity limits changing with temperature value.

  • Upper Limit Delay
    Number of intervals that the Upper Limit value should be exceeded before elproMONITOR informs user about the deviation can be entered here

  • Consider logging intervals…
    Entering a tick causes invalid values (no connection, sensor failure) to be taken into consideration as a violation of the alarm

Delete

Opens the window for permanently deleting the selected Sensor Limit Profile. No further data will be recorded. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add New Profile are displayed for editing.

Close

Close appears in details section and closes the current window and returns to the Sensor Limit Profile overview.

8. Sensor Issue Profiles

A - Details

With a left click on a certain line the detail view sensor group opens. The detailed view includes a list of all Sensor Issue Profiles from the overview Sensor Issue Profiles and the details of the selected object. The applicable functions for the selected Issue Profile are described in III - Applicable functions and are:

  • Report

  • Add New Profile

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The Sensor Limit Profile is opened by clicking on the "Sensor Issue Profile" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the Sensor Issue Profile The following information is available for each Sensor Limit Profile:

  • Sensor Issue Profile Name - name of the Sensor Issue Profile

  • No Connection Alarm- Data flow between sensor and the elproMONITOR is interrupted

  • Sensor Failure- The following states are treated as sensor failures:

    • Value overflow in measurement range

    • Value underflow in measurement range

    • Faulty sensor

    • Unplugged sensor

  • Low Battery Notification- The battery level of the wireless sensor is low. This means the battery is almost empty. The battery level is monitored independently of the elproMONITOR, It is performed by the I/O module itself

  • Radio Strenght Warning- The Radio strenght is low, this may lead to communication failures

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Add New Profile

The details in the view are replaced by the following parameters for creating a new Sensor Issue Profile:

 

 

Sensor Issue Profile:

  • Sensor Issue Profile Name
    Name of the Sensor Issue Profile for monitoring with elproMONITOR and for easy identification in the reports. The Sensor Issue Profile must be provided with a unique name.

  • No Connection Alarm
    The alarm is activated only by ticking the hook.

  • No Connection Delay
    Number of intervals that the No Connection Failure should occure before elproMONITOR informs user about the issue can be entered here

  • Sensor Failure
    The issue is activated only by ticking the hook.

  • Sensor Failure Delay
    Number of intervals that the Sensor Failure should occure before elproMONITOR activates the deviation, can be entered here

  • Low Battery Notification
    The issue is activated only by ticking the hook.

  • Radio Strenght Warning
    The issue is activated only by ticking the hook.

  • Radio Strenght Warning Delay
    Number of intervals that the poor radio strenght should occure before elproMONITOR activates the deviation, can be entered here

  • Signal to Noise Ratio Threshold
    The user defined value to set the custom radio streng; taking in to account the ratio between, signal and noise level.

  • One of the following options should be selected to set the alarm level for radio strenght

    • Weak Radio Strenght

    • Bad Radio Strenght

    • Custom Radio Strenght

Delete

Opens the window for permanently deleting the selected Sensor Issue Profile. No further data will be recorded. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add New Profile are displayed for editing.

Close

Close appears in details section and closes the current window and returns to the Sensor Issue Profile overview.

9. Digital Input Profiles

A - Details

With a left click on a certain line the detail view Digital Input Profile opens. The detailed view includes a list of all Digital Input Profiles from the overview Digital Input Profiles and the details of the selected object. The applicable functions for the Digital Input Profile are described in III - Applicable functions and are:

  • Report

  • Add New Profile

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The Digital Input Profile is opened by clicking on the "Digital Input Profile" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the Digital Input Profile The following information is available for each Profile:

  • Digital Input Profile Name - name of the Digital Input Profile

  • Logic- Defined contact status used as an alarm trigger

  • Delay- Delay time entered in logging interval step

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Add New Profile

The details in the view are replaced by the following parameters for creating a new Digital Input Profile:

 

 

Digital Input Profile:

  • Digital Input Profile Name
    Name of the Digital Input Profile for monitoring with elproMONITOR and for easy identification in the reports. The Digital Input Profile must be provided with a unique name.

  • I/O Module Type
    Here the correct I/O Module type can be selected. Options are ECOLOG-PRO 4DI or ECOLOG-NET

  • Mode
    Here the Log mode can be selected, there following options available

    • STANDARD The status at the moment when the interval was started is shown by the Digital Input

    • TIME MONITORING The duration of the contact status (open, closed) as a percentage of the logging interval is used as the activation is shown by the Digital Input (min. 200 ms)

    • EDGE COUNTER The number of contact status changes (rising, falling) per logging interval is used as the activationmis shown by the Digital Input (min. 200 ms)

  • Text if Input=1 or 0
    Text field for entering the message text

  • Logic
    Alarm if Input = 1 Alarms if the Digtial Input Status changes from 0 to 1
    Alarm if Input = 0 Alarms if the Digital Input Status changes from 1 to 0

  • Delay
    Delay time, enter in logging interval steps

 

 

Mode Time Monitor:

  • Border greater than, Border less than
    Limit values in % of the logging interval.

  • Text if outer Border, Text if inner Border
    Text field for entering the message text

 

 

Mode Edge Counter:

  • Border Greater Than, Border less than
    Limit values in number of edge changes.

  • Text if outside limits, Text if inside limits
    Text field for entering the message text.

Delete

Opens the window for permanently deleting the selected Digital Input Profile. No further data will be recorded. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add New Profile are displayed for editing.

Close

Close appears in details section and closes the current window and returns to the Digital Input Profile overview.

10. Recipient Profiles

A - Details

With a left click on a certain line the detail view Recipient Profile opens. The detailed view includes a list of all Recipient Profiles from the overview Recipient Profiles and the details of the selected object. The applicable functions for the Recipients Profile are described in III - Applicable functions and are:

  • Report

  • Add New Profile

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The Recipient Profile is opened by clicking on the "Recipient Profiles" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the Recipient Profiles The following information is available for each Profile:

  • Recipient Profile Name - name of the Recipient Profile

  • E-Mail- Shows if the E-Mail receiving option for the Profile enabled or disabled

  • Aggregated Alarm Email- Enabled or Disabled

  • SMS- Enabled or Disabled

  • Plugin- Enabled or Disabled

  • Repeat Notification- Enabled or Disabled

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Add New Profile

The details in the view are replaced by the following parameters for creating a new Recipient Profile:

 

 

Create New Recipient Profile:

  • Recipient Profile Name
    Name of the Recipient Profile for monitoring with elproMONITOR and for easy assigning of the recipients. The Recipient Profile must be provided with a unique name.

  • E-Mail
    The e-mail alarm is activated by ticking the checkbox. All information needed to identify an issue is automatically contained in the e-mail
    To, Cc, Subject: This information is used to address the e-mail.
    Text This field should contain information such as process information, responsibilities, and instructions, and is attached to each e-mail. Relevant Information can be added by selecting from the menu on the right side of the Text field. As default all informations are selected

  • Send Test E-Mail is to test the functions

 

 

Aggregated Alarm Email:

This option is used to receive a summary of the active and/or inactive deviations in a specific time period as an e-mail. This means the sensor must be configured accordingly in order to obtain a deviation
The aggregated email alarm is activated by ticking the checkbox

  • Aggregation Interval of Change
    Interval time as minutes can be selected from the drop down menu

  • To, Cc, Subject: This information is used to address the e-mail.
    Text This field should contain information such as process information, responsibilities, and instructions, and is attached to each e-mail. Relevant Information can be added by selecting from the menu on the right side of the Text field. As default all informations are selected

  • Send Test Aggregated E-Mail is to test the functions

 

 

SMS:
The SMS alarm is activated by ticking the checkbox

  • SMS Number
    The mobile phone number that elproMONITOR should send the alarm information to.

  • SMS Text
    This field should contain information such as process information, responsibilities, and instructions, and is attached to each SMS. Relevant Information can be added by selecting from the menu on the right side of the Text field. As default all informations are selected

  • Send Test SMS is to test the functions

 

 

 

Digital Outputs:

  • Digital Output 1, Digital Output 2
    Selection list of configured digital outputs.

  • Plugin
    Plugin, Parameters: This is a customer-specific software module. It is produced by Elpro-Buchs AG

  • Test Plugin is to test the functions

 

 

 

 

Repeat Notification:
The Repeat Notification is activated by ticking the checkbox

  • Repeat Notification Integral
    The interval time in minutes can be input here

Delete

Opens the window for permanently deleting the selected Recipient Profile. No further data will be recorded. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add New Profile are displayed for editing.

Close

Close appears in details section and closes the current window and returns to the Recipient Profile overview.

 

11. Schedule Profiles

The scheduler is used to provide a day time-dependent control over the warning and alarm functions of elproMONITOR. For each sensor or digital input it is possible to define a schedule which switches between several alarm profiles. There are 2 alarm profiles (SET A, SET B) and a deactivation option. The defined profiles are assigned to the sensors and digital inputs with CREATE/EDIT NEW SENSOR or CREATE/EDIT NEW DIGITAL INPUT

A - Details

With a left click on a certain line the detail view Schedule Profile opens. The detailed view includes a list of all Schedule Profiles from the overview Schedule Profiles and the details of the selected object. The applicable functions for the Schedule Profile are described in III - Applicable functions and are:

  • Report

  • Add New Profile

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The Schedule Profile is opened by clicking on the "Schedule Profiles" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the Schedule Profiles The following information is available for each Profile:

  • Schedule Profile Name - name of the Schedule Profile

  • Profile Set A- Shows the details of the Set A Profile

  • Profile Set B- Shows the details of the Set B Profile

  • Deactivated- Shows the details of the Deactivated Profile

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Add New Profile

The details in the view are replaced by the following parameters for creating a new Schedule Profile:

 

 

Create New Schedule Profile:

  • Schedule Profile Name
    Name of the Schedule Profile for monitoring with elproMONITOR. The Schedule Profile must be provided with a unique name.

  • By Day Time (…)
    To change the state of a particular field, highlight it with the mouse pointer and change the state by clicking on the corresponding button. It is not possible to change the time grid resolution

  • Example
    SET A - Weekdays (Green)
    SET B - Weekends (Purple)
    DEACTIVATED - Deactivated days (Yellow)
    CLEAR - The entire profile is overwritten by SET A
    Selected: Wed 04:30 - 05.0 am

 

 

  • By Date
    Specify the alarm period by entering the calendar day and the alarm profile

  • Add New
    Add a new calendar day and profile

  • Remove
    Deletes the input

  • By Digital Inputs
    Profile Set B by Digital Input - The selected digital input switches between alarm profiles SET A and SET B.
    Deactivated by Digital Input -The selected digital input deactivates all the alarm functions controlled by this profile.

Delete

Opens the window for permanently deleting the selected Schedule Profile. No further data will be recorded. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add New Profile are displayed for editing.

Close

Close appears in details section and closes the current window and returns to the Schedule Profile overview.

 

12. Data Destination Profiles

The target directory for exporting data from elproMONITOR is defined in this profile

A - Details

With a left click on a certain line the detail view Data Destination Profile opens. The detailed view includes a list of all Data Destination Profiles from the overview Data Destination Profiles and the details of the selected object. The applicable functions for the Data Destination Profile are described in III - Applicable functions and are:

  • Report

  • Add New Profile

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The Data Destination Profile is opened by clicking on the "Data Destination Profiles" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the Data Destination Profiles The following information is available for each Profile:

  • Data Destination Profile Name - name of the Data Destination Profile

  • Type- Server type that the data will be saved

  • Path- The path to the local or network drive or the directory

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Add New Profile

The details in the view are replaced by the following parameters for creating a new Data Destination Profile:

 

Create New Destination Profile:

  • Data Destination Profile Name
    Name of the Data Destination Profile for saving monitoring data with elproMONITOR. The Data Destination Profile must be provided with a unique name.

  • Connection Test
    Function to test the data export. The test is ended by an OK or NOK confirmation

 

 

Data Destination:

  • Type
    FTP - The exported data are saved on a FTP server. Only passive FTP is currently supported.
    NETDRIVE - The exported data are saved on a network drive. • Path Directory on a network drive (e.g.: \\192.168.100.20\DataExport)
    DRIVE - The exported data are saved locally

  • Path
    Directory on the server incl. server address (z.B.: ftp:// meinserver.com/export)
    Directory on a network drive (e.g.: \\192.168.100.20\DataExport)
    Local drive and directory (e.g.: C:\export)

  • Login name, password
    Login information for this server
    The domain or IP address of the target computer must always be before the login name (e.g. DOMAIN\Username or 192.168.100.20\Username)

Delete

Opens the window for permanently deleting the selected Data Destination Profile. No further data will be recorded. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add New Profile are displayed for editing.

Close

Close appears in details section and closes the current window and returns to the Data Destination Profile overview.

13. Data Export Profiles

The subfolder used for saving, the name and content of the exported file are defined in this profile.

A - Details

With a left click on a certain line the detail view Data Export Profile opens. The detailed view includes a list of all Data Export Profiles from the overview Data Export Profiles and the details of the selected object. The applicable functions for the Data Export Profile are described in III - Applicable functions and are:

  • Report

  • Add New Profile

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The Data Export Profile is opened by clicking on the "Data Export Profiles" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the Data Export Profiles The following information is available for each Profile:

  • Data Export Profile Name - name of the Data Export Profile

  • Type- Server type that the data will be saved

  • Path- The path to the local or network drive or the directory

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Add New Profile

The details in the view are replaced by the following parameters for creating a new Data Export Profile:

 

 

Create New Data Export Profile:

  • Data Export Profile Name
    Name of the Data Export Profile for saving monitoring data with elproMONITOR. The Data Export Profile must be provided with a unique name.

  • Output-Format
    By setting the tick, the corresponding output formats are activated
    CSV - The export takes place as a CSV file
    PDF - The export takes place as a PDF file
    One PDF containing all sensors - A PDF file with all sensors will be created. The first page of the PDF document contains the overlay of all sensors

  • TimeZone
    Time zone that the data export will be done, can be selected from the drop down menu
    Adjust for Daylight Savings Time - if ticked, elproMONITOR will adjust the daylight saving automatically

 

 

  • File-Description
    Subfolder - Subfolder options can be selected by left click on them. Left arrow will carry the selected option to Subfolder area and relevant data will be exported. Order in the Subfolder area can be adjusted by up and down arrows.
    A selected Subfolder option can be deselected by carrying it back to Subfolder options area by right arrow.

  • Prefix for Filename - Text field for entering the chosen prefix

  • Filename - File name defined from the file options and order of the file options can be adjusted the same way as described in Subfolder section

  • Overwrite existing files - Entering a tick in the checkbox means that an existing file is overwritten by a new file with the same designation

 

 

  • CSV-Configuration
    CSV-Token - CSV-Token options can be selected by left click on them. Left arrow will carry the selected option to CSV-Token area and relevant data will be exported. Order in the CSV-Token area can be adjusted by up and down arrows.
    A selected CSV-Token option can be deselected by carrying it back to CSV-token options area by right arrow.

  • Dateformat
    Dateformat can be selected from the dropdown menu. Date format can be selected either purely numeric format or Month is abbreviated

  • Timeformat
    It is possible to select that the time be displayed in either a 12 hour or 24 hour time format

  • Decimaldescriptor
    The decimal can be shown as a point or comma

  • CSV-Separator
    It is possible to select either a semi-colon or comma. If a comma is selected as a decimal separator, the comma cannot be used as a CSV-separator

Delete

Opens the window for permanently deleting the selected Data Export Profile. No further data will be recorded. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add New Profile are displayed for editing.

Close

Close appears in details section and closes the current window and returns to the Data Export Profile overview.

Application Settings

14. Export Schedule Tasks

A - Details

With a left click on a certain line the detail view Export Schedule Task opens. The detailed view includes a list of all Export Schedule Tasks from the overview Export Schedule Tasks and the details of the selected object. The applicable functions for the Export Schedule Task are described in III - Applicable functions and are:

  • Report

  • Add New Task

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The Export schedule Tasks is opened by clicking on the "Export Schedule Tasks" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the Export Schedule Tasks The following information is available for each Profile:

  • Export Schedule Task Name - name of the Export Schedule Task

  • Interval- Time Span between two exports

  • Data Safety Clearance - The time of data export is delayed by the Data Safety Clearance to allow reloading of non-directly transmitted values

  • Unit - The unit for the Data Safety Clearance

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Add New Profile

The details in the view are replaced by the following parameters for creating a new Export Schedule Task:

 

 

Create New Export Schedule Task:

  • Export Schedule Task Name
    Name of the Export Schedule Task for saving monitoring data with elproMONITOR. The Export Schedule Task must be provided with a unique name.

  • Data Export Profile
    Allocation of a data export profile

  • Data Destination Profile
    Allocation of a data destination profile

  • Recipient Profile
    Assignment of the recipient

  • Create Testfile / Send Testfile
    Tests the function for the seleckted profiles

 

 

  • Interval
    The time span between two exports can be selected: hourly, daily, weekly or monthly. At the beginning of the new interval plus a possible data safety clearance, the report is created over the last interval. The beginning and the end of the time window can not be changed. For example, for a monthly interval, it is not possible to choose the time window from mid-month 1 to mid-month 2; It is always from the beginning to the end of the month

  • Data Safety Clearance
    The time of data export is delayed by the Data Safety Clearance to allow reloading of non-directly transmitted values (e.g., due to a connection break to the measurement modules)
    For example, if a 3-day Data Safety Clearance is set for a scheduled monthly export, the automatic export does not start in the early morning of the first day of a month for the previous month, but 3 days later, this means in the early morning of the 4th day of the new month. Thus, missing values of the previous month can be reloaded during these three days and would thus also be included in the export.

  • Unit
    Depending on the selected interval, the unit for the Data Safety Clearance is hours, days or months

 

 

  • Sensors
    By selecting the sensor from the dropdown menu and adding it, the sensors for the report are defined

  • Sensor Name
    Selected sensors are listed here

  • Remove - Removes the Sensir from the list

 

 

  • Digital Inputs
    By selecting the Digital Input from the dropdown menu and adding it, the Digital Input for the report are defined

  • Digital Input Name
    Selected Digital Inputs are listed here

  • Remove - Removes the Digital Input from the list

Delete

Opens the window for permanently deleting the selected Export Schedule Tasks. No further data will be recorded. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add New Task are displayed for editing.

Close

Close appears in details section and closes the current window and returns to the Export Schedule Tasks overview.

15. Comment Templates

A - Details

With a left click on a certain line the detail view Comment Template opens. The detailed view includes a list of all Comment Templates from the overview Comment Templates and the details of the selected object. The applicable functions for the Comment Templates are described in III - Applicable functions and are:

  • Report

  • Add New Template

  • Delete

  • Edit

  • Close

B - Quick Links

The following Quick Links are available. (See III - Applicable functions)

  • Edit

  • Delete

I - Devices Settings

The Comment Templates is opened by clicking on the "Comment Templates" menu item in the Settings menu.

II - Detail Column

This area contains basic information about the Comment Templates The following information is available for each Profile:

  • Comment Template Name - name of the Comment Template

  • Text- Comment text assigned to the template

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Add New Profile

The details in the view are replaced by the following parameters for creating a new Comment Tempate:

 

 

Create New Comment Template:

  • Comment Template Name
    Name of the Comment Template for saving comments with elproMONITOR. The Comment Template must be provided with a unique name.

  • Text
    Text assigned to the Comment Template

  • Allow Edit
    If ticked comment text can be edite

Delete

Opens the window for permanently deleting the selected Comment Templates. No further data will be recorded. Deletion is possible only after selecting a comment template or output of a comment and authentication with the password.

Edit

The same parameters as in >> Add New Template are displayed for editing.

Close

Close appears in details section and closes the current window and returns to the Comment Template overview.

16. E-Mail

These are the settings for E-Mail server

I - Devices Settings

The E-Mail server setting page is opened by clicking on the "E-Mail" menu item in the Settings menu.

II - E-Mail Server Settings

 

E-Mail:

  • E-Mail Server Type
    E-Mail Server type can be selected from dropdown menu

  • E-Mail Server (SMTP) or (Microsift Office 365)
    Required Host or IP for SMTP Server or Tenand, Cliend IDs for Microsift Office 365 Server can be input here

  • Server Requires Authentication
    If ticked User name and Password can be input here

  • Test connection
    Function for testing the e-mail connection between the elproMONITOR software and the email server. The test is ended by an OK or NO

 

 

  • Sender
    Name - Name of the elproMONITOR platform

  • E-Mail - email of the sender

  • Send Queue
    This function repeats e-mail transmission until the e-mail is sent successfully. The queue of pending messages is cleared by deactivating this function.
    • Repeat Time Interval Delay time between repeated e-mails.
    • Maximum Queue Time Maximum time to send the e-mail repeatedly

  • Keep Alive E-Mail
    This function is used to send a check e-mail at regular intervals. This ensures that the notification works in case of alarm.
    • Maximal Time between Messages - Delay time between Keep Alive E-Mails.
    • Message Send Time - Time when the Keep Alive E-Mail is sent.
    • Recipient Profiles - Please refer to Recipient Profile section

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Save

Save appears when an input is changed and saves the changes.

Cancel

Cancels the changes without saving and returns to the E-Mail section

17. SMS

I - Devices Settings

The SMS property setting page is opened by clicking on the "SMS" menu item in the Settings menu. Dropdown menu for the type and properties of the modem in use

II - E-Mail Server Settings

 

SMS:

  • USB
    - COM port
    - Baud Rate (Standard 57600)
    - SIM Card PIN Code

  • Test Signal Strength
    Function for testing the SMS connection between the elproMONITOR software and the SMS server. The test is ended by an OK or NOK confirmation.

 

 

SMS:

  • Ethernet
    - IP Address
    - Port Number (Standard 10001)
    - SIM Card PIN Code

  • Test Signal Strength
    Function for testing the SMS connection between the elproMONITOR software and the SMS server. The test is ended by an OK or NOK confirmation.

 

 

  • Send Queue
    This function repeats SMS transmission until the SMS is sent successfully. The queue of pending messages is cleared by deactivating this function.
    Repeat Time Interval - Delay time between the repeated SMS.
    Maximum Queue Time - Maximum time to send the SMS repeatedly

  • Keep Alive SMS
    This function is used to send a check SMS at regular intervals. This ensures that the notification works in case of alarm.
    Maximal Time between Messages - Delay time between Keep Alive SMS Texts
    Message Send Time - Time when the Keep Alive SMS is sent.
    Recipient Profile - Please refer to the Recipient Profile Section

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Save

Save appears when an input is changed and saves the changes.

Cancel

Cancels the changes without saving and returns to the E-Mail section

18. System Issues

I - Devices Settings

The System Issue message forwarding function setting page is opened by clicking on the "System Issues" menu item in the Settings menu. Dropdown menu is for selecting the Recipient Profile

II - System Issues

 

System Issues:

  • Recipient Profile
    The Recipient Profile for forwarding the Issue message can be selected from the dropdown menu

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Save

Save appears when an input is changed and saves the changes.

Cancel

Cancels the changes without saving and returns to the System Issues section

19. License

I - Devices Settings

The License page is opened by clicking on the "Licenses" menu item in the Settings menu.

II - Licenses Page

 

License:

  • One license is used for each sensor and digital input. The license continues to be assigned for a sensor in Retired state, i.e. which only exists to display historical data. When a sensor is added, a check is made whether there is a free license. Deleting a sensor will not result in a refund of fees. However, the assigned license is released and can be used for a new sensor.

 

 

  • License Order
    Step 1 - The customer requires additional sensor licenses and inputs the required amount to Requested number of licenses field and clicks Create License Order.
    Step 2 - Customer sends the created order to Elpro Buchs AG.

  • Upload License
    Step 1 - Customer receives a License file from Elpro Buchs AG.
    Step 2 - Customer Uploads the received file to elproMONITOR. Upload activates the new licenses

III - Applicable Functions

The following functionalities can be executed here.

Report*

A >> elproMONITOR configuration report with all selected parameters is created.

Save

Save appears when an input is changed and saves the changes.

Cancel

Cancels the changes without saving and returns to the Licenses section

User Settings

20. Profile

I - Devices Settings

The User Profile page is opened by clicking on the "Profile" menu item in the Settings menu.

II - Profile

 

Profile:

The Profile function is used to edit user-specific defaults.

  • Language - At present the software is only available in German and English.

  • Display Time Zone (only applies to current user) - Defines the time zone used for the display.

  • Adjust for Daylight Saving Time - Tick the checkbox to adjust between summer and winter time automatically.

  • Show Retired Sensors - "Retired" sensors can only be shown for this user in all views by ticking this checkbox.